Zero water consumption
Rejects heat outdoors with zero water consumption — no water treatment, blowdown, or Legionella risk.
Available Now
Four-fan dry cooler for mid-scale immersion or facility-water loops.
Part number BSK-DC-360
Rev. A
Rejects heat outdoors with zero water consumption — no water treatment, blowdown, or Legionella risk.
4 × Krubo K-EC910-W460-10 (Ø910mm) EC axial fans, variable-speed for quiet, efficient operation.
Corrosion-resistant coil construction for long service life in outdoor deployment.
Operates from -25°C to +60°C ambient, 0–95% RH non-condensing.
Crane lift points and container-top/side-by-side mounting brackets ship standard for rapid installation.
Optional BITSINK health-monitoring suite integration for remote condition monitoring.
| Configuration | 4 fans, horizontal top-discharge |
|---|---|
| Rated Heat Rejection | 360 kW |
| Warranty | 2-Year Limited Warranty on Parts and Labor |
| Overall L × W × H | 120.0 × 86.9 × 67.5 in (3.0 × 2.2 × 1.7 m) |
|---|---|
| Dry / Operating Weight | 760 kg (1,675 lb) / 920 kg (2,028 lb) |
| Housing | Sheet metal, powder-coated white |
| Fluid In/Out | ANSI 150LB DN80 SS flange (2 total) |
|---|---|
| Working Fluid | Water (closed-loop, inhibited) |
| Power Input | 380/480V, 3-phase, 50/60 Hz |
| Coil Internal Volume | 160 L (42.3 US gal) |
|---|---|
| Fin / Tube Material | Aluminum fin / copper tube, 5/8 in TP2 copper |
| Coil Geometry | 6 rows × 56 tubes × 2,720mm |
| Fan Model | Krubo K-EC910-W460-10 (Ø910mm EC axial) |
|---|---|
| Airflow / Sound | 140,000 m³/h free-air total · 87 dB(A) @ 1m |
| Fan Power | 8,480 W (8.48 kW) total |
| Ambient Temperature | -25°C to +60°C |
|---|---|
| Relative Humidity | 0–95% RH |
| Details | integrated electrical box with breakers, crane lift points, container-top/side-by-side mounting brackets, BITSINK health-monitoring suite. |
|---|